beautypg.com

Table 5 — co, Sensor standard settings – Bryant DURAPAC PLUS 581B User Manual

Page 22

background image

22

Table 5 — CO

2

Sensor Standard Settings

LEGEND

ppm — Parts Per Million

IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED

Adjust evaporator-fan speed to meet jobsite conditions.
Tables 6A and 6B show fan rpm at motor pulley settings for
standard and alternate motors. Tables 7 and 8 show evapora-
tor fan motor data. Table 9 shows EconoMi$er IV pressure
drop. Table 10 shows sound data. Refer to Tables 11-28 for
fan performance data. See Fig. 38 for Perfect Humidity™ sys-
tem static pressure drop.

NOTE: Before adjusting fan speed, make sure the new fan
speed will provide an acceptable air temperature rise range
on heating as shown in Table 1.

To change fan speed:

1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.

See Fig. 39.

3. Loosen movable pulley flange setscrew (see Fig. 40).
4. Screw movable flange toward fixed flange to increase

fan speed and away from fixed flange to decrease fan

speed. Increasing fan speed increases load on motor.
Do not exceed maximum speed specified in Table 1.

5. Set movable flange at nearest keyway of pulley hub

and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)

To align fan and motor pulleys:

1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from

mounting plate.

To adjust belt tension:

1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for

proper belt tension (

1

/

2

-in. deflection with 8 to 10 lb of

force) and tighten mounting nuts (see Fig. 39).

3. Adjust bolt and nut on mounting plate to secure

motor in fixed position.

Table 6A — 581B Fan Rpm at Motor Pulley Setting With Standard Motor*

*Approximate fan rpm shown (standard motor/drive).

Table 6B — 581B Fan Rpm at Motor Pulley Setting With High-Static Motor*

*Approximate fan rpm shown (high-static motor/drive).

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface w/Standard
Building Control System

Proportional

Any

0-10V

4-20 mA

0-2000

1000

50

2

Proportional

Any

2-10V

7-20 mA

0-2000

1000

50

3

Exponential

Any

0-10V

4-20 mA

0-2000

1100

50

4

Economizer

Proportional

15

0-10V

4-20 mA

0-1100

1100

50

5

Proportional

20

0-10V

4-20 mA

0- 900

900

50

6

Exponential

15

0-10V

4-20 mA

0-1100

1100

50

7

Exponential

20

0-10V

4-20 mA

0- 900

900

50

8

Health & Safety

Proportional

0-10V

4-20 mA

0-9999

5000

500

9

Parking/Air Intakes/
Loading Docks

Proportional

0-10V

4-20 mA

0-2000

700

50

UNIT
581B

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036

1044

1008

971

935

898

862

826

789

753

716

680

048

1185

1144

1102

1061

1019

978

936

895

853

812

770

060 (single and 3-phase)

1460

1425

1389

1354

1318

1283

1248

1212

1177

1141

1106

1070

1035

072

1585

1538

1492

1445

1399

1352

1305

1259

1212

1166

1119

UNIT
581B

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060

1685

1589

1557

1525

1493

1460

1428

1396

1364

1332

1300

072

1685

1589

1557

1525

1493

1460

1428

1396

1364

1332

1300