VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS

A. Disconnect Switch

The optional disconnect switch is non-fused. The switch has
the capability of being locked in place for safety purposes.

B. Perfect Humidity™ Dehumidification System

Perfect Humidity system operation can be controlled by field
installation of a Bryant-approved humidistat device (Fig. 13),
or light commercial Thermidistat™ device (Fig. 14). To install
the humidistat device:

1. Route humidistat cable through hole provided in unit

corner post.

2. Feed wires through the raceway built into the corner

post to the 24-v barrier located on the left side of the
control box. See Fig. 12. The raceway provides the
UL-required clearance between high-voltage and low-
voltage wiring.

3. Use a wire nut to connect humidistat cable into low-

voltage wiring as shown in Fig. 15.

To install Thermidistat device:

1. Route Thermidistat cable through hole provided in

unit corner post.

2. Feed the wires through the raceway built into the cor-

ner post to the 24-v barrier located on the left side of
the control box. See Fig. 12. The raceway provides the
UL-required clearance between high and low voltage
wiring.

3. A field-supplied relay must be installed between the

Thermidistat device and the Perfect Humidity circuit
(recommended relay: HN612KK324). See Fig. 16. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-pres-
sure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.

% RELATIVE HUMIDITY

Fig. 13 — Accessory Field-Installed Humidistat Device

Fig. 14 — Light Commercial Thermidistat Device

Fig. 15 — Typical Perfect Humidity Dehumidification System

Humidistat Wiring (208/230-v Unit Shown)

C

Contactor (Compressor)

CB

Circuit Breaker

CR

Cooling Relay

DHR

Dehumidify Relay

DSV

Discharge Solenoid Valve

HU

Humidistat

LPS

Low Pressure Switch

LSV

Liquid Line Solenoid Valve

LTLO

Low Temperature Lockout

TRAN

Transformer

Terminal (Unmarked)

Splice

Factory Wiring

Accessory or Optional Wiring

LEGEND