C. Convenience Outlet

An optional convenience outlet provides power for rooftop
use. For maintenance personnel safety, the convenience out-
let power is off when the unit disconnect is off. Adjacent unit
outlets may be used for service tools. An optional “Hot Out-
let” is available from the factory as a special order item.

D. Manual Outdoor-Air Damper

The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.

Assembly:

1. Determine quantity of ventilation required for build-

ing. Record amount for use in Step 8.

2. Remove outdoor-air opening panel. Save panels and

screws. See Fig. 17.

3. Remove evaporator coil access panel. Separate hood

and screen from basepan by removing the 4 screws
securing them. Save all screws.

4. Replace evaporator coil access panel.

5. Place hood on front of outdoor-air opening panel. See

Fig. 18 for hood details. Secure top of hood with the 4
screws removed in Step 3. See Fig. 19.

6. Remove and save 6 screws (3 on each side) from sides

of the manual outdoor-air damper.

7. Align screw holes on hood with screw holes on side of

manual outdoor-air damper. See Fig. 18 and 19.
Secure hood with 6 screws from Step 6.

8. Adjust minimum position setting of the damper blade

by adjusting the manual outdoor-air adjustment
screws on the front of the damper blade. See Fig. 17.
Slide blade vertically until it is in the appropriate
position determined by Fig. 20. Tighten screws.

9. Remove and save screws currently on sides of hood.

Insert screens. Secure screens to hood using the
screws. See Fig. 19.

ROOF TOP UNIT

R
C

Y1

Y2

G

W1

W2

PINK

PINK

RED

24 V

FROM
PERFECT HUMIDITY
SYSTEM LLSV

R1

T STAT WIRES

LCT

R
C

Y1

Y2

G

W1

W2

DEHUM

OC

R1

PERFECT HUMIDITY SYSTEM

PINK

LTLO

CB

3.2 AMPS

Fig. 16 — Typical Rooftop Unit with Perfect Humidity™ Dehumidification System with Thermidistat Device

LEGEND

CB

Circuit Breaker

LCT

Light Commercial Thermidistat™ Device

LLSV — Liquid Line Solenoid Valve
LTLO — Low Temperature Lockout

OUTDOOR
AIR OPENING
PANEL

3 SCREWS
(SIDE)

Fig. 17 — Damper Panel with Manual

Outdoor-Air Damper Installed

Fig. 18 — Outdoor-Air Hood Details