Table 2A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet

Table 2B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet

LEGEND

*The values listed in this table do not include power exhaust. See table at right for

power exhaust requirements.

†Used to determine minimum disconnect per NEC.

**Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.

2. Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage.
3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent voltage
imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not available

NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.

Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 32.8 amps + 1.6 amps = 34.4 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for
the power exhaust will be 15 amps per NEC.

UNIT
581B

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

(each)

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY*

MINIMUM UNIT

DISCONNECT SIZE†

Min

Max

Qty

RLA

LRA

FLA

FLA

FLA

MCA

MOCP**

FLA

LRA

036

(3 Tons)

208/230-1-60

187

254

1

16.0

88.0

0.7

4.9

.60

25.6/25.6

30/30

25/25

101/101

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.60

18.5/18.5

25/25

18/18

90/90

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

9.0

20

9

46

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

7.3

20

7

37

048

(4 Tons)

208/230-1-60

187

254

1

23.7

126.0

0.7

4.9

.60

35.2/35.2

45/45

34/34

139/139

208/230-3-60

187

254

13.5

93.0

0.7

4.9

.60

22.5/22.5

30/30

22/22

106/106

460-3-60

414

508

6.4

46.5

0.4

2.2

.30

10.6

20

10

54

575-3-60

518

632

6.4

40.0

0.4

2.2

.30

10.1

20

10

46

060

(5 Tons)

208/230-1-60

187

254

1

28.8

169.0

1.5

8.8

.60

46.3/46.3

60/60

45/45

216/216

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.60

28.9/28.9

35/35

28/28

168/168

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

14.7

20

14

84

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

11.6

20

12

68

072

(6 Tons)

208/230-3-60

187

254

1

20.5

156.0

1.4

5.8

.60

32.8/32.8

40/40

32/32

200/200

460-3-60

414

508

9.6

75.0

0.6

2.6

.30

15.2

20

15

97

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

12.2

20

12

74

UNIT
581B

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

(each)

IFM

COMBUSTION

FAN MOTOR

POWER

SUPPLY

WITH OUTLET*

MINIMUM UNIT

DISCONNECT SIZE†

Min

Max

Qty

RLA

LRA

FLA

FLA

FLA

MCA

MOCP**

FLA

LRA

036

(3 Tons)

208/230-1-60

187

254

1

16.0

88.0

0.7

4.9

.60

31.6/31.6

35/35

30/30

106/106

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.60

24.5/24.5

30/30

24/24

95/95

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

11.7

20

11

48

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

9.5

20

9

38

048

(4 Tons)

208/230-1-60

187

254

1

23.7

126.0

0.7

4.9

.60

41.2/41.2

50/50

39/39

144/144

208/230-3-60

187

254

13.5

93.0

0.7

4.9

.60

28.5/28.5

35/35

27/27

111/111

460-3-60

414

508

6.4

46.5

0.4

2.2

.30

13.3

20

13

56

575-3-60

518

632

6.4

40.0

0.4

2.2

.30

12.2

20

12

47

060

(5 Tons)

208/230-1-60

187

254

1

28.8

169.0

1.5

8.8

.60

52.3/52.3

60/60

50/50

221/221

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.60

34.9/34.9

40/40

34/34

173/173

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

17.4

20

17

87

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

13.8

20

13

70

072

(6 Tons)

208/230-3-60

187

254

1

20.5

156.0

1.4

5.8

.60

38.8/38.8

45/45

37/37

205/205

460-3-60

414

508

9.6

75.0

0.6

2.6

.30

17.9

20

17

99

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

14.3

20

14

75

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.9

N/A

15

CRPWREXH022A01

3.3

N/A

1.32

15

CRPWREXH023A01

N/A

1.8

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

1.0

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

7
457