Pdf 13, 13 of 20 – MAMAC Systems IP-PC-101-44-VDC User Manual
Page 14

SECTION 2 - Output Configuration
To configure the outputs, click on the
Configuration icon in the navigation bar and select
Outputs
. The four outputs can be controlled by the inputs or can be programmed to switch on
and off based on a time schedule. Outputs can also have both sensor input based setpoint
control AND time control concurrently. If an output has both setpoint control AND time control
programmed, the appliance will ignore setpoint control during
On time and the output will
remain
On based on time schedule. However, if the output is scheduled Off based on time
schedule, setpoint control can switch it on.
Double click
Output 1
icon and a new page will be served up to configure the output. In the
Name
field please enter a unique identifier for the output up to 20 alpha and/or numeric
characters. If the output is only controlled by a sensor input, no additional configuration is
required.
If time based control is desired on an output, please click
Enabled
(default is
Disabled)
. Click
the radio button
On
for each day time control is desired and fill in the start and stop time in 24
hour format. Click
Save
. Output is configured.
2.6.0
13.34:59
May 9, 2008
IP Sensor Appliance:
Main
Manual Control
Data Logging
Configuration
MAMAC UNO
Configuration | Password/Clock
Copyright 2008
c
www.mamacsys.com
R
Registered trademark MAMAC Systems, Inc.
Output 1
Output 2
Output 3
Output 4
: Fan
: Pump
: XXXX
: XXXX
OUTPUT CONFIGURATION
Output 2
Output 1
10:00
15:30
17:30
17:30
17:30
17:30
17:30
15:30
10:00
05:00
05:00
05:00
05:00
05:00
TIME CONTROL
Start:
Stop:
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
09:00
17:00
19:00
19:00
19:00
19:00
19:00
17:00
09:00
06:00
06:00
06:00
06:00
06:00
Start:
Stop:
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Output 3
© Copyright 2008
DN IS-IPPC101.1
® Registered trademark MAMAC SYSTEMS, Inc.
13 of 20