MAMAC Systems TE-705 User Manual
Rohs, Model te-705, Technical information

SPECIFICATIONS
Platinum RTD Sensors:
±0.1% @ 32°F (0°C), Alpha: 385 per DIN 43760
Nickel RTD Sensors (#2):
±0.5°C @ 0°C (32°F), 5,000 PPM/K T.C.R.
Nickel RTD Sensors (#4):
±0.5°F @ 70°F (21.1°C), 6,000 PPM/K T.C.R.
Balco RTD Sensors:
±0.5°F @ 70°F (21.1°C), 4,300 PPM/K T.C.R.
Thermistor Sensors:
±0.2°C interchangeability @ 77°F (25°C)
Operating Temperature:
-40°F to 210°F (-40°C to 100°C)
Probe Material:
3/8" (9 mm) Bendable aluminum
Flange Material:
Galvanized Steel
Steel NEMA-1 (IP-30):
18 Ga. Galvanized Steel
Steel NEMA-4 (IP-65):
18 Ga. Cold Rolled Steel, Powder coated
Warranty:
Five Years (Lifetime on Moisture Migration)
EMC Conformance:
EN 55022, 55024, 61000-3-3,
61000-4-2, 3, 4, 5, 6 & 11
U.S. PATENT NO. 6592254, 7465087
For Additional Information See TE-705 Data Sheet
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
[email protected] • www.mamacsys.com
Model TE-705
Technical Information
TI.705-03
DUCT AVERAGING TEMPERATURE SENSORS
RoHS
ORDERING INFORMATION: TE-705-
INSTALLATION
TEMP SENSOR
PROBE
LENGTH
B Galvanized Steel
Enclosure
(NEMA-1 / IP-30)
C Painted Steel
Enclosure
(NEMA-4 / IP-65)
A 6 ft (1.8 m)
B 12 ft (3.6 m)
C 24 ft (7.2 m)
1 100-Ohm Platinum RTD
2 1,000-Ohm Nickel RTD
(5,000 PPM)
3 1,000-Ohm Platinum RTD
4 1,000-Ohm Nickel RTD
(6,000 PPM)
5 1,000-Ohm Balco RTD
7 10,000-Ohm NTC Thermistor
(Type III)
8 10,000-Ohm NTC Thermistor
(Carel)
10 3,000-Ohm NTC Thermistor
12 10,000-Ohm NTC Thermistor
(Type II)
13 5,000-Ohm NTC Thermistor
14 1,035-Ohm Silicon PTC
15 100,000-Ohm NTC Thermistor
16 10,000 ohm NTC Thermistor
..........
(Eliwell)
17 20,000-Ohm NTC Thermistor
18 2,252-Ohm NTC Thermistor
21 1,800-Ohm NTC Thermistor
Example: TE-705-B-10-B-1: Duct Averaging Temp Sensor, NEMA-1 enclosure,
12 ft. bendable 3/8" aluminum, 3,000 ohm NTC thermistor.
1 Bendable
3/8"
Aluminum
PROBE
TYPE
For Resistance vs. Temperature tables, please refer to TI.700-11.
Inspection
Requirements
INSTALLATION
Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
package and inspect the device for obvious damage.
Return damaged products.
•
Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
•
Appropriate accessories
•
Two #8 self-tapping mounting screws (not provided)
•
Training: Installer must be a qualified, experienced technician.