MAMAC Systems PR-243 User Manual
Rohs, Model pr-243, Technical information

Accuracy*: ± 1% FS
Maximum Pressure: 40 PSIG
Supply Voltage: 12–40 VDC
12–35 VAC (VDC output units only)
Supply Current: VDC Units – 10 mA max.
mA Units – 20 mA max.
Enclosure: 18 Ga C. R. Steel NEMA 4 (IP-65)
Finish: Baked on enamel – PMS2GR88B
EMC Conformance: EN 55022, 55024, 61000-3-3,
61000-4-2, 3, 4, 5, 6 & 11
Compensated Temp Range: 0°F to 180°F (-18°C to 82°C)
T. C. Error: ±0.025%/°F (.03%/°C)
Media Compatibility: Clean dry air or any inert gas
Port Connection: 5/32" I.D.; 1/4" Brass Hose Barb
Environmental: 10–90%RH Non-Condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga max.
Load Impedance: 3K ohms max. at 40 VDC (mA
output units)
1K ohms min. (VDC output units)
Weight: Enclosure 1.0 lbs. (.45 kg)
*Includes non-linearity, hysteresis and non-repeatability
SPECIFICATIONS
Inspection
Requirements
Mounting
For Additional Information See PR-243 Data Sheet
INSTALLATION
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
[email protected] • www.mamacsys.com
Model PR-243
Technical Information
TI.243-06
PNEUMATIC PRESSURE SENSOR
Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
package and inspect the device for obvious damage.
Return damaged products.
Warning:
• Do not use on oxygen service, in an explosive/hazardous
environment, or with flammable/combustible media.
• Disconnect power supply before installation to prevent
electrical shock and equipment damage.
• Make all connections in accordance with the job wiring
diagram and in accordance with national and local
electrical codes. Use copper conductors only.
Caution:
• Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and wiring to prevent equipment
damage.
• Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMA Type 4
housings are intended for outdoor use primarily to provide
a degree of protection against wind-blown dust, rain, and
hose-directed water.
• Do not exceed ratings of the device.
The PR-243 must be mounted on a vertical surface with the
1/4" brass hose barb pointing left or right. Refer to
Figure 7 for
mounting dimensions.
1. Remove the transducer cover using a Phillips head
screwdriver.
2. Select the mounting location.
3. Mount transducer on a vertical surface with two #8 self-tapping
screws (not provided).
4. Pull wires through bottom of enclosure and make necessary
connections.
5. Replace cover and make pneumatic connections.
•
Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
• Appropriate accessories
• Two #8 self-tapping mounting screws (not provided)
• Training: Installer must be a qualified, experienced technician
Wiring
Use maximum 12 AWG wire for wiring terminals. Use flexible
1/4" O.D., 5/32" I.D. tubing for pressure connections. Refer to
Figures 1, 2, 3, & 4 for wiring information. and Figures 5 & 6 for
switch designations.
(Wiring Instructions continued on pages 2 and 3.)
RANGE
OUTPUT
R1 (psig)
R2 (psig)
R3 (psig)
R4 (kPa)
0 to 20 / 0 to 10 / 0 to 5
0 to 30 / 0 to 15 / 0 to 7.5
3 to 15
0 to 140 / 0 to 70 / 0 to 35
(4–20 mA 2-wire)
(0–5 VDC/0–10 VDC
field selectable)
mA
VDC
R5 (kPa)
R6 (kPa)
0 to 200 / 0 to 100 / 0 to 50
20 to 100
ORDERING INFORMATION: PR-243-
RoHS