Pdf 11, 11 of 20 – MAMAC Systems IP-PC-101-44-VDC User Manual
Page 12

SECTION 2 - Sensor Inputs, Email Alert &
Setpoint Control Configuration
From the navigation bar, click/highlight
Configuration and pick Inputs. The appliance will
serve up the input configuration page. Based on the sensors selected, click the appropriate
radio button
(0-5VDC, 0-10VDC or Digital). Next click Save. All inputs will be
automatically configured to accept the specified sensor input.
(Default is 0-10 VDC input).
Next double click
Input 1 and a new page will open up to configure input number 1.
Name: Type in an appropriate name for the input e.g: Room Temp or Humidity. Sensor name
can be any alpha and/or numeric characters up to 18 characters.
Min Value: Enter the minimum value of the sensor range in this field. For example if the
sensor output is 0-10VDC for 0 - 100ºF temperature range, enter
0 as min value. Similarly, if
the sensor range is -30 to + 130°F, the min value would be
-30. Default value is 0.
Max Value: Enter the maximum value for the sensor range in this field. For the above
examples, the maximum value for 0 to 100ºF would be
100 and for -30 to +130ºF would be
130. Default value is 0.
Units: Enter the desired units for the sensor input up to 6 alpha characters only.
WARNING: Do not use numeric characters in the Units field.
2.5.0
2.5.1
2.5.2
2.5.3
2.5.4
13.34:59
May 9, 2008
IP Sensor Appliance:
Main
Manual Control
Data Logging
Configuration
MAMAC UNO
Configuration | Password/Clock
Copyright 2008
c
www.mamacsys.com
R
Registered trademark MAMAC Systems, Inc.
0.0
100.0
F
Name:
Min Value
Max Value
Real Value Limits and Units
Input 1
Lab Temp
Units
Alert Enabled
Lower Value
Upper Value
Alert Wait
Attach Log
Email Alert Configuration
69.0
70.0
Alert Enabled
1 Sec
Output Control
Lesser than
or equal to
Greater than
or equal to
Relay Control Settings
1
67.0
69.0
Relay off
Relay on
Alert Disabled
On
Off
On
Off
rademark MAMAC Systems, Inc.
n
Save
© Copyright 2008
DN IS-IPPC101.1
® Registered trademark MAMAC SYSTEMS, Inc.
11 of 20