Troubleshooting and fault elimination

5

EDKMZ2221IB DE/EN/FR 6.0

39

l

H1fehler−stoerungen

Remedy

Cause

Card module

Remedy

Cause

Text

Display

E 3

Check drive

No program in basic device.

Load program into basic device.

Basic device is not ready for
operation.

Reset TRIP in basic device and − if
necessary − disconnect mains.

E 4

Repeat (T1 or T2)

AIF access protection is activated
in the basic device (C0096/1

¹

0)

Deactivate AIF access protection
in the basic device (C0096/1 = 0)

The data transmission has been
truncated or was faulty

Restart data transmission

E 5

Technology drive
needed

PLC program contains technology
functions which cannot be
transferred to the existing basic
device.

Servo PLC: use version "T".
ECS: use version ECSxA, ECSxS,
ECSxM, or ECSxP.
If required, contact Lenze service.

E 6

Drive not
supported

Basic device is unknown or not
supported.

Use card module with supported
basic devices only (

^ 24).

E 7

Prog. is defective

Stored data of the selected
program memory location are
faulty

Choose other program memory
location

E 8

Program
incompatible

The program is incompatible to
the basic device

Press key T3 and write compatible
program on the memory card.

E F

Format card (T3)

Memory card is not formatted

Press button T3 to format the
memory card.
During formatting the letter

F

is

indicated on the 7−segment
display.

Memory card is defective

Replace memory card