Electrical installation
Power terminals
4
82
EDKCSEE040 DE/EN/FR 4.0
4.3
Power terminals
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when the device is touched in the event
of a fault.
Protective measures:
ƒ
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor
diameter 10 mm
2
or PE conductor must be connected twice)
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.
ƒ
All power connections are plug connections and are coded. The connector
set for the ECSZE000X0B power supply modules must be ordered
separately.
ƒ
Installation of cables acc. to EN 60204-1.
ƒ
The cables used must comply with the approvals required for the
respective application (e.g. VDE, UL, etc.).