21
RG-MHLON
LonWorks Network Variables
nciRampUpTm
Definition
Network config input SNVT_time_sec nciRampUpTm
Explanation
This configuration property is used to set the ramp up time of the drive (i.e. the time
that it will take for the drive to ramp the motor from 0.00Hz to Max Frequency).
Valid Range
0.1 to 3600.0 sec
(Refer to MCH Installation and Operation Manual for the actual minimum boundary)
The value 0xFFFF represents invalid data.
Default Value 30.0 sec
nciRampDownTm
Definition
Network config input SNVT_time_sec nciRampDownTm
Explanation
This configuration property is used to set the ramp down time of the drive (i.e.
the time that it will take for the drive to ramp the motor from Max Frequency to
0.00Hz).
Valid Range
0.3 to 3600.0 sec
(Refer to MCH Installation and Operation Manual for the actual minimum boundary)
The value 0xFFFF represents invalid data.
Default Value 30.0 sec
nciLocation
Definition
Network config input SNVT_str_asc nciLocation
Explanation
This configuration property can optionally be used to provide more descriptive
physical location information than can be provided by the Neuron Chip’s 6-byte
location string. The location relates to the object and not to the node.
Valid Range
31 characters
Default Value Empty spaces
nciDrvSpdScl
Definition
Network config input SNVT_lev_percent nciDrvSpeedScale
Explanation
Default value for nviDrvSpdScl.
Valid Range
-163.840% to 0.000 % or 0.000% to +163.835%
The value 0x7FFF represents invalid data.
Default Value 100.000%