Drive Setup & Programming
3.5 Serial Communication Setup
The factory default values of the drive parameters have been set to allow immediate serial communications
(without serial stop/start and serial speed commands). For serial speed and/or serial start/stop control,
modify the setting of Drive Parameter #30 (Control). The drive parameters that are required for serial
communications, including Drive Parameter #30, are described herein.
24 AUTO SOURCE
This parameter must be set to KEYPAD for the drive speed or setpoint to be modified
over the network.
30 CONTROL
This parameter should be set to accommodate the specific application intent:
NORMAL
Serial start/stop and serial speed commands are invalid.
NORM NO HAND Same as NORMAL except the HAND/OFF/AUTO, herein referred to
as H/O/A, is limited to settings of OFF and AUTO.
SERIAL SPEED
Serial start commands are invalid. Serial speed commands are
valid in AUTO.
S SPD/NO HAND Same as SERIAL SPEED except H/O/A is limited to settings of OFF
and AUTO.
SERIAL AUTO
Serial start/stop and serial speed commands are valid in AUTO.
This setting forces the drive to be started via the serial link when
in AUTO.
S AUTO/NO HND Same as SERIAL AUTO except H/O/A is limited to settings of OFF
and AUTO.
The STOP command issued when LonWorks (LON) parameter nviEmrgOvrd is set to EMERG_SHUTDOWN
is accepted regardless of the H/O/A switch position.