Safety instructions – Lenze 8200 vector 15kW-30kW User Manual
Page 10

Safety instructions
Residual hazards
l
10
EDK82EV303 EN 1.0
Device protection
ƒ
All pluggable terminals can only be plugged in or unplugged when the controller is
disconnected from the power supply!
ƒ
Frequent mains switching (e.g. inching mode via mains contactor) can overload and
destroy the input current limitation of the controller:
– Therefore at least 3 minutes must pass between two switch−on operations.
Motor protection
ƒ
Certain drive controller settings can overheat the connected motor:
– E. g. long−time operation of the DC injection brake.
– Long−time operation of self−ventilated motors at low speeds.
Protection of the machine/system
ƒ
Drives can reach dangerous overspeeds (e. g. setting of high output frequencies in
connection with motors and machines not suitable for this purpose):
– The drive controllers do not provide protection against such operating conditions.
For this purpose, use additional components.
J
Warnings!
ƒ
The device has no overspeed protection.
ƒ
Must be provided with external or remote overload protection.
ƒ
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum (240 V devices) or 500 V maximum
(400/500 V devices) resp.
ƒ
Use 60/75 °C or 75 °C copper wire only.
ƒ
Shall be installed in a pollution degree 2 macro−environment.