Communication manual 8400 motec PROFIBUS

Parameter reference

Parameters relevant for PROFIBUS communication

86

L

EDS84DMOTPBUS EN 3.0 - 11/2011

C13882

C13885

C13886

Parameter | Name:

C13882 | Monitoring time: Watchdog

Data type: UNSIGNED_32

Index: 10693

d

= 29C5

h

Display of the watchdog monitoring time determined by the PROFIBUS master

• A change in the watchdog monitoring time is immediately effective.

• Monitoring starts with the receipt of the first telegram.

• When a value of "0" is displayed, the monitoring function is deactivated.

Permanent interruption of PROFIBUS communication ( 69)

Display area

(min. value | unit | max. value)

0

ms

4294967295

Subcodes

Info

C13882/1

Watchdog monitoring time

C13882/2

DP-V1 MSAC2

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Delete process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

Selection of the process data which the controller will process in the event of a PROFIBUS failure in order to maintain

internal communication.
Selection list

(Lenze setting printed in bold)

0 Use of most recent master PDOs
1 PDOs are set to the value 0'

;

Read access ; Write acces … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13886 | Set ext. diagnostic bit in case of

Data type: BITFIELD_8

Index: 10689

d

= 29C1

h

Bit-coded selection of the error responses in the drive unit causing the external diagnostic bit ("diag bit") to be set

(see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).

• The diagnostic bit is sent to the PROFIBUS master by the communication unit and is evaluated separately there.

• The diagnostic bit is always set when a system error or an error message by the safety module occurs.

• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
Value is bit-coded:

Bit 0 Error
Bit 1 Reserved
Bit 2 Reserved
Bit 3 Warning locked
Bit 4 Reserved

... ...

Bit 7 Reserved

;

Read access ; Write acces … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT