Profibus Watchdog: Monitoring time elapsed [0x01bc8130]
Profibus: State Data_Exchange left [0x01bc8131]
Profibus Watchdog: DP-V1 MSC2 elapsed [0x01bc8132]
Response (Lenze setting printed in bold)
Setting:
(; adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Permanent interruption of communication to PROFIBUS
master.
• See also chapter "
.
Check cables and terminals.
Note:
We recommend to set "Warning locked" for the response
(no drive-relevant response).
Response (Lenze setting printed in bold)
Setting:
(; adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
Data exchange via PROFIBUS has been stopped.
• See also chapter "
.
Check cables and terminals.
The slave must receive new parameterisation and
configuration files from the master in order to be able to
exchange data again.
Response (Lenze setting printed in bold)
Setting:
(; adjustable response)
:
No response System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
Permanent interruption of communication to PROFIBUS
master.
• See also chapter "
.
Check cables and terminals.
Note:
We recommend to set "Warning locked" for the response
(no drive-relevant response).