Installation
Electrical installation
5.2.3
Bus cable specification
Bus cable length
The bus cable length depends on the baud rate used:
Tip!
For high baud rates, we recommend taking the use of optical fibres into
consideration.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission
path.
• Bus lengths of several kilometres are also possible with higher baud rates.
The bus length is ...
– independent of the baud rate;
– dependent on the optical fibre used.
Note!
Only use cables that correspond to the given specifications of the PROFIBUS user
organisation.
Area
Values
Cable resistance
135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length
≤
30 nF/km
Loop resistance
< 110 Ω/km
Core diameter
> 0.64 mm
Core cross-section
> 0.34 mm
2
Cores
Twisted in pairs, insulated and shielded
Baud rate
Length
9.6 ... 93.75 kbps
1200 m
187.5 kbps
1000 m
500 kbps
400 m
1500 kbps
200 m
3000 ... 12000 kbps
100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations
should only be selected as high as required for the application.