Electrical installation
Mounting steps
EDK94AZMS DE/EN/FR/ES/IT 8.0
52
l
H1_E_INST−−−−(DUMMYSEITEVOR)−−−
Terminal data
Max. conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
E94AZMS0034
2.5
14
0.5 ... 0.6
4.42 ... 5.31
PH1
E94AZMS0094
4
12
E94AZMS0184
10
8
1.2 ... 1.5
10.6 ... 13.3
E94AZMS0314
PE connection data
Æ
Starting torque
!
[mm]
[Nm]
[lb−in]
E94AZMS0034
M5
3.0
26.5
SW 8
E94AZMS0094
E94AZMS0184
E94AZMS0314
Standard device
Cable X302
Labelling
Description
1
2
3
Filter output conductor (lead with wire end ferrule, colour
BK)
PE
Output−side PE conductor (lead with M5 fork−type cable
lug, colour GN/YE)
SSP94FF007
Mounting steps
Proceed as follows to connect the filter:
1. Connect the filter output cable (X302) to terminal X100 of the standard device.
2. Connect the mains cable to terminal X301.
3. Attach the supply−side PE conductor to the PE conductor screw using a ring or
fork−type cable lug.
– The PE connection must comply with EN 61800−5−1.