8 final works, Final works, Final works 8 – Lenze E94APNE User Manual
Page 46: 8final works, Danger
Final works
8
l
46
EDK94PNE36 DE/EN/FR/ES/IT 3.1
8
Final works
{
Danger!
Dangerous voltage!
Depending on the device, the DC−bus voltage is still charged for
approx. 3 ... 20 min after switching off the mains voltage.
ƒ
The state of charge is not indicated!
ƒ
On synchronous motors self−discharge only starts after a possible feedback
operation has been completed.
ƒ
Discharging the DC bus in a controlled manner via the brake chopper/brake
resistor requires the external 24 V supply (
^ digital input DI1).
Possible consequences:
ƒ
Death or severe injuries when touching the terminals.
Protective measures:
ƒ
Before starting work on the system check that it is deenergised.
ƒ
Wait at least 3 minutes after switching off the mains voltage.
ƒ
Only remove deenergised standard devices from the installation backplanes
and do not touch any terminals.
How to proceed:
ƒ
Adjust the setting for the mains voltage/brake chopper threshold to the mains
Setting of mains voltage/brake chopper threshold
2
Pos.
3
U
LN
[V]
U
BRmax
[V]
1
500 V
480 V
400 V
230 V
ON
MAINS
12
500
790
OFF
OFF
480
765
ON
OFF
400
725
OFF
ON
230
390
ON
ON
94APNEDS01
ƒ
Switch on the 24 V supply
ƒ
Check the operating status by means of the LED display
If you want to continue commissioning:
ƒ
Switch on the mains