3 technical data, 1 general data and operating conditions, Technical data – Lenze E94APNE User Manual
Page 36: General data and operating conditions, 3technical data
Technical data
General data and operating conditions
3
l
36
EDK94PNE36 DE/EN/FR/ES/IT 3.1
3
Technical data
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
Approval
In preparation: UL
UL 508C
Industrial Control Equipment, file no. 132659
Supply system data
Supply forms
With earthed
*
point
Unrestricted use
IT systems
Unrestricted use
Observe instructions about special measures concerning the
connected axis controllers!
Noise emission
EN 61800−3
Conducted: cannot be specified because dependent on the
conditions present in the interconnected system
Radiation: category C3
Noise immunity (according to requirements of EN 61800−3)
Electrostatic discharge
(ESD)
EN 61000−4−2
8 kV for air discharge,
4 kV for contact discharge to housing
Radio frequency
Conducted
EN 61000−4−6
150 kHz ... 80 MHz, 10 V/m 80 % AM (1 kHz)
Radiation (housing)
EN 61000−4−3
80 MHz ... 1000 MHz, 10 V/m 80 % AM (1 kHz)
Protection of persons and device protection
Enclosure
EN 60529
IP 20
Not in the wire range of
the terminals on the
motor side
NEMA 250
Protection against contact to
type 1
Insulation resistance
EN 61800−5−1
Overvoltage category III
Derating at and above 2000 m AMSL: overvoltage category II
Isolation of control circuits EN 61800−5−1
Safe mains isolation through double/reinforced insulation.
Short−circuit strength
EN 61800−5−1
DC−bus connection: not short−circuit−proof
Brake resistor connection: full
Control connections: full
Discharge current
EN 61800−5−1
> 3.5 mA
Observe regulations and
safety instructions!
Cyclic mains switching
Cyclic mains switching of five times in five minutes is fully
permissible.
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertical
Mounting clearances
Above/below
³ 80 mm / ³ 120 mm
Observe the device−related
notes on mounting.
To the sides
Side−by−side mounting without
any clearance