4technical data – Lenze EZVxx00−001 Power supply unit AC 400V 5A-20A User Manual
Page 26
![background image](/manuals/565734/26/background.png)
Technical data
EDKZV1200 DE/EN/FR/ES/IT 1.0
26
l
H1_Daten−−−−(DUMMYSEITEVOR)−−−
Input data
Power supply unit AC 400 V, DC 24 V
5 A
10 A
20 A
Turn−on time
< 1 s after applying the mains voltage
Transient surge voltage protection
varistor
Mains voltage range
3 AC 320 V − 0 % ... 575 V + 0 %, 45 Hz − 0 % ... 65 Hz + 0 %
Current
consumption
AC 400 V 3 x 0.4 A
3 x 0.6 A
3 x 1.1 A
AC 480 V 3 x 0.3 A
3 x 0.6 A
3 x 1.0 A
Starting current limitation /
I
2
t (+25 °C)
typ. < 15 A /
< 3.0 A
2
s
typ. < 15 A /
< 4.0 A
2
s
typ. < 15 A /
< 1.0 A
2
s
Mains buffering at
rated load
AC 400 V typ. > 50 ms
typ. > 40 ms
typ. > 23 ms
AC 480 V > 50 ms
> 40 ms
> 25 ms
Recommended back−up fuse
Circuit−breaker (charact. B or C)
6 A / 10 A / 16 A
Output data
Power supply unit AC400 V, DC 24 V
5 A
10 A
20 A
Rated output voltage U
N
DC 24 V / ± 1 %
Setting range of the output voltage
DC 22.5 ... 28.5 V
Start of unlimited capacitive loads
yes
Residual ripple / switching peaks (20
MHz)
<
100 mV
SS
at rated values
Can be connected in parallel
to increase redundancy and power
Resistance to return supply
DC 35 V
l
Output current I
BOOST
at
– convection cooling
– V
rated
– −25 ... +40 °C
7.5 A
15 A
27 A
l
Rated output current I
rated
at
– convection cooling
– V
rated
– −25 ... +60 °C
5 A
10 A
20 A
Current limitation in case of short
circuit
< 7.5 A
< 15 A
< 27 A