Electrical installation, Block diagram, Connection terminals – Lenze EZVxx00−001 Power supply unit AC 400V 5A-20A User Manual
Page 20: 2electrical installation
![background image](/manuals/565734/20/background.png)
2
Electrical installation
Block diagram
EDKZV1200 DE/EN/FR/ES/IT 1.0
20
l
H1_E_INST−funktion
2
Electrical installation
Block diagram
L1
L2
L3
PE
+
+
-
-
DC OK
13
14
DC 22.5
… 28.5 V
3 AC 320
… 575 V
1
ezv1201_07
Connection terminals
ƒ Power supply unit AC 400 V, DC 24 V, 5 A
ƒ Power supply unit AC 400 V, DC 24 V, 10 A
Input terminals
Output terminals
Rigid terminal
0.2 ... 6.0 mm
2
(AWG 24 ... 10)
0.2 ... 6.0 mm
2
(AWG 24 ... 10)
Flexible terminal with wire end
ferrule with plastic collar
0.2 ... 4.0 mm
2
(AWG 24 ... 10)
0.2 ... 4.0 mm
2
(AWG 24 ... 10)
Stripping length
7 mm
7 mm
Tightening torque
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
ƒ Power supply unit AC 400 V, DC 24 V, 20 A
Input terminals
Output terminals
Rigid terminal
0.2 ... 6.0 mm
2
(AWG 24 ... 10)
0.5 ... 16.0 mm
2
(AWG 20 ... 6)
Flexible terminal with wire end
ferrule with plastic collar
0.2 ... 4.0 mm
2
(AWG 24 ... 10)
0.5 ... 10.0 mm
2
(AWG 20 ... 6)
Stripping length
8 mm
10 mm
Tightening torque
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
1.2 ... 1.5 Nm