Technical data, Technical data 4 – Lenze EZVxx00−001 Power supply unit AC 400V 5A-20A User Manual
Page 25

Technical data
4
EDKZV1200 DE/EN/FR/ES/IT 1.0
25
l
H1_Daten−−−−(DUMMYSEITEVOR)−−−
4
Technical data
General data /
operating conditions
Power supply unit AC400 V, DC 24 V
5 A
10 A
20 A
Conformity
CE
l
Low−Voltage Directive (2006/95/EG)
l
EMC Directive (2004/108/EG)
Approval
UL508 Industrial Control equipment (file no. E123528)
Vibration resistance
to IEC 68−2−27
up to 30 g
Climatic conditions
to EN 60 721
Class 3K3
Degree of pollution
to EN 50 178
2
Permissible temperature ranges
l
Storage: −40 °C ... +85 °C
l
Operation: −25 °C ... +70 °C,
the output current must be reduced by 2.5 %/°C above a
temperature of +60 °C
Humidity
< 95 % , at +25 °C, no condensation
Free space
> 50 mm, above / below
Dimensions (B ×
H × T)
73 Ч 130 Ч 125
mm
85 Ч 130 Ч 125
mm
160 Ч 130 Ч 125
mm
Weight
0.95 kg
1.1 kg
1.93 kg
General electrical data
Power supply unit AC 400 V, DC 24 V
5 A
10 A
20 A
Degree of protection
IP 20
Class of protection
I (with PE connection)
Leakage current to PE
< 3.5 mA
MTBF
to IEC 1709 (SN 29 500)
> 500 000 h
Max. power loss
(idle state/ rated load)
3 W / 17 W
4 W / 28 W
7 W / 47 W
Efficiency
at AC 230 V and rated values
> 88 %
> 90 %
> 91 %