Commissioning, 3 parameter menu – Lenze SMD 0-25kW-4-0kW User Manual
Page 15
![background image](/manuals/565708/15/background.png)
Lenze 13435747 EDBSX03 v17
EN, DE, FR, IT, ES
13
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
C00
Password entry
0
0 999 Visible only when password is active
(see C94)
C01
Setpoint source
0 Analog input (terminal 8; see C34)
1 Code c40
Observe notes about c40
C02
Load Lenze setting
0 No action/loading complete
• C02 = 1... 4 only possible with
OFF
• C02 = 2 : C11, C15 = 60 Hz
1 Load 50 Hz Lenze settings
2 Load 60 Hz Lenze settings
3 Load OEM settings
4 Translate
WARNING!
C02 = 1... 3 overwrites all settings! TRIP circuitry may be disabled!
Check codes CE1...CE3.
NOTE
If an EPM that contains data from a previous software version is installed, C02 =
4 converts the data to the current version.
CE1
Configuration -
Digital Input E1
1
1 Activate fixed setpoint 1 (JOG1)
• Use C37...C39 to adjust fixed setpoints
• Activate JOG3: Both terminals = HIGH
2 Activate fixed setpoint 2 (JOG2)
3 DC braking (DCB)
See also C36
4 Direction of rotation
LOW = CW rotation
HIGH = CCW rotation
5 Quick stop
Controlled deceleration to standstill,
active LOW; Set decel rate in C13 or
c03
6 CW rotation
7 CCW rotation
CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected
CE2
Configuration -
Digital Input E2
4
8 UP (setpoint ramp-up)
UP = LOW and DOWN = LOW: Quick
stop; Use momentary NC contacts
9 DOWN (setpoint ramp-down)
10 TRIP set
Active LOW, triggers
EEr
(motor coasts
to standstill)
NOTE:
NC thermal contact from the
motor can be used to trigger this input
CE3
Configuration -
Digital Input E3
3
11 TRIP reset
See also c70
12 Accel/decel 2
See c01 and c03
13 Deactivate PI
Disables PI function for manual control
14 Activate fixed PI setpoint 1
• Use C37...C39 to adjust fixed
setpoints
• Activate fixed PI setpoint 3: Both
terminals = HIGH
15 Activate fixed PI setpoint 2
NOTE
A
CFG
fault will occur under the following conditions:
• E1...E3 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
4.3
Parameter menu