Installation
3.2.4 Control terminals
NOTE
LOW = 0 to +3V, HIGH = +12 to +30V.
Protection against contact
• All terminals have basic isolation (single insulating distance)
• Protection against contact can only be ensured by additional measures (i.e. double insulation)
STOP!
In the case of a Spinning Motor:
To bring free-wheeling loads such as fans to a rest before starting the drive, use the DC
injection braking function (“Auto-DCB”). Starting a drive into a freewheeling motor creates
a direct short-circuit and may result in damage to the drive.
Confirm motor suitability for use with DC injection braking.
Terminal
Data for control connections
(printed in bold = Lenze setting)
7
Reference potential
8
Analog input
0 … 10 V
(changeable under C34)
input resistance: >50 kΩ
(with current signal: 250 Ω)
9
Internal DC supply for setpoint potentiometer
+10 V, max. 10 mA
20
Internal DC supply for digital inputs
+12 V, max. 20 mA
28
Digital input Start/Stop
LOW = Stop
HIGH = Run Enable
R
i
= 3.3 k
Ω
E1
Digital input configurable with CE1
Activate fixed setpoint 1 (JOG1)
HIGH = JOG1 active
E2
Digital input configurable with CE2
Direction of rotation
LOW = CW rotation
HIGH = CCW rotation
E3
Digital input configurable with CE3
Activate DC injection brake (DCB)
HIGH = DCB active
K12
Relay output (normally-open contact)
configurable with C08
Fault (TRIP)
AC 250 V / 3 A
DC 24 V / 2 A … 240 V / 0.22 A
K14