beautypg.com

Lenze ESVZAR0 RS-485 User Manual

Page 31

background image

29

CMVMB401C

Troubleshooting and fault elimination

11

Troubleshooting and Fault Elimination

11.1 Faults

Table 18 lists faults relating to Modbus communication. Refer to section 9.2.10, Present Fault, for a list of drive faults.

Table 18: Communication Faults

Display

Status

Cause

Remedy

n

Module to Drive communication

time out

Connection between drive and module is not

made.

Check cable and connection between module

and drive

n

Network Time-out Fault

Drive under NETWORK control and network

communications have been lost.

See parameters P425, P426

11.2 Troubleshooting

Table 19 lists common communication errors and suggests methods to verify and correct the problem.

Table 19: Communication Errors

Symptom

Possible Cause

Remedy

No communication from the drive

Module is not initialized properly

• Verify the module connection
• Check P400 and P402

Incorrect Modbus settings

• Use P403 to reset Modbus parameters.
• Verify P410 and P411, P412

Improper wiring

• Check wiring between the Modbus Network and

communication module.

• Ensure that terminal block is properly seated.
• Check connection between module and drive.

Modbus write commands are ignored or
return exceptions.

“Network Enabled terminal is either open
or not configured.

Configure one of the input terminals (P121, P122, or
P123) to “Network Enabled” function (selection 9)
and close the corresponding contact.

Drive stops without obvious reason

Modbus message monitoring time-out
occurred. The timeout reaction is set to
STOP, Quick stop or Inhibit..

Modify the setting of time-out time (P425) or the
reaction to the time-out (P426).