Drive registers – Lenze ESVZAR0 RS-485 User Manual
Page 25

23
CMVMB401C
Drive Registers
9.2.5 Run Status - Register #26
The low byte (DL) of register 26 provides the Operational Status as listed in Table 9.
Table 9: Operational Status - Register #26 DL
Value
Description
0
Fault Lockout
1
Fault
2
Start Pending
3
IDE not done
4
Inhibit
5
STOP
6
Lower Transistors switching on
7
Run IDE
8
Run
9
Accel
10
Decel
11
Decel Override
12
DC Brake
13
Flying Restart
14
Slow Current Limit
15
Fast Current Limit
16
Sleep
9.2.6 Actual Direction - Register #27
The high byte (DH) of register 27 provides the actual rotational direction of the motor.
Table 10: Actual Rotational Direction - Register #27 DH
Setting
Direction
0
Forward
1
Reverse
9.2.7 Control Mode - Register #27
The low byte (DL) of register 27 provides the Control Mode as listed in Table 11.
Table 11: Control Mode - Register #27 DL
Value
Control Mode
Description
0
Local
Start commands from drive keypad (P100 = 0 or 4)
1
Terminal
Start commands from control wiring on drive terminal Strip (P100 = 1, 4 or 5)
2
Remote Keypad Only
Start commands from optional remote keypad (P100 = 2 or 5)
3
Network Only
Start commands from Network, but Network control is not active (P100 = 3)
4
Network Control
Start commands from Network and Network control is active (P100 = 0, 1, 3 or 4)