Resistance / potentiometer
Resistance transmitter
Voltage
Measuring circuit monitoring
MoRe5-MoRe41
0 to 2000 °C
± 0.2 %
Cold junction
Pt1000 internal
Cold junction accuracy
±
1 K
a
All accuracies given in % refer to the maximum measuring range
Designation
Measuring range
Measuring accuracy
a
a
All accuracies given in % refer to the maximum measuring range
Resistance / potentiometer
Linearization: 0 to 100 %
>
50
Ω
to
≤
400
Ω
>
400
Ω
to
≤
4000
Ω
>
4000
Ω
to
≤
10000
Ω
±
400 m
Ω
±
4
Ω
±
10
Ω
Resistance / potentiometer
Linearization: Resistance in
Ω
> 50
Ω
to
≤
10000
Ω
±
0.1 %
Connection type
2-wire or 3-wire circuit
Lead compensation
Not required for 3-wire circuit (max. admissible 11
Ω
per line).
Max. configurable lead wire resistance for 2-wire circuit: 22
Ω
.
Designation
Measuring range
Measuring accuracy
a
a
All accuracies given in % refer to the maximum measuring range
Resistance transmitter
>
50
Ω
to
≤
400
Ω
>
400
Ω
to
≤
4000
Ω
>
4000
Ω
to
≤
10000
Ω
±
400 m
Ω
±
4
Ω
±
10
Ω
Connection type
3-wire connection
Requirement
R
e
+ R
a
+ R
s
≤
10000
Ω
and R
e
+ R
a
≤
1/3 R
s
Designation
Measuring range
Measuring accuracy
a
a
All accuracies given in % refer to the maximum measuring range
Voltage
0 to 50 mV
±
0.1 %
Measuring probe
Detection of
overrange / underrange
Detection of
probe /
cable short circuit
Detection of
probe /
cable break
Thermocouple
Yes / Yes
No
Yes
RTD temperature probe
Yes / Yes
Yes
Yes
Resistance / potentiometer
Yes / Yes
Yes
Yes
Resistance transmitter
No / No
No
No
Voltage
Yes / Yes
No
Yes
Designation
Standard
Measuring range
Measuring accuracy
a