Technical data – JUMO 707530 Ex-i Repeater Power Supply / Input Isolating Amplifier Data Sheet User Manual
Page 2

2012-08-22/00584206
Data Sheet 707530
Page 2/4
JUMO GmbH & Co. KG
Telefon: +49 661 6003-727
Hausadresse:
Moritz-Juchheim-Straße 1, 36039 Fulda, Germany
Telefax: +49 661 6003-508
Lieferadresse:
Mackenrodtstraße 14, 36039 Fulda, Germany
E-Mail:
Postadresse:
36035 Fulda, Germany
Internet: www.jumo.net
Technical data
Measuring input
Output
General data
Data communication (bypass)
Voltage supply
Connection data
Input signal current
0 to 20 mA
4 to 20 mA
Transmitter supply voltage
> 16 V (at 20 mA)
Signal output
Current output
Output signal voltage
0 V to 5 V (internal resistance, 250 Ω, 0,1%)
1 V to 5 V (internernal resistance, 250 Ω, 0,1%)
Output signal current
0 mA to 20 mA (active)
4 mA to 20 mA (active)
0 mA to 20 mA (passive, external source voltage 14 to 26 V)
4 mA to 20 mA (passive, external source voltage 14 to 26 V)
Burden/output load current output
< 600 Ω (current output)
Number of channels
1
Transmission error max.
< 0,1 % (of end value)
Transmission error typical
< 0,05 % (of end value)
Temperature coefficient max.
< 0,01 %/K
Ambient temperature (operation)
-20 °C to 60 °C (any installation position)
Ambient temperature
(storage/transport)
-40 °C to 80 °C
Admissible air humidity (operation)
10 % to 95 % (no condensation)
Step response (10 - 90%)
< 600 µs (for step 4 mA to 20 mA)
Status display
LED green (supply voltage)
Width
12.5 mm
Height
104 mm
Depth
114.5 mm
Flammability class according to UL 94 V0
Material of case
Polyamide (PA 6.6)
Color
Gray
EMC
EN 61326-1
HART function
Yes
Supported protocols
HART
Range of supply voltage
24 to 230 V AC/DC, -20 % to +10 %, 50 to 60 Hz
Current consumption
< 80 mA (at 24 V DC)
Power consumption
< 1,6 W
Conductor cross section rigid min.
0.2 mm²
Conductor cross section rigid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG/kcmil
min.
24