Technical data
Case
Electrical data
Case
Sheet steel, galvanized
Protection type
IP 00 according to EN 60529
Switching socket
Polyester resin molding compound, black
Max. permissible ambient
temperature
For transport and storage: -40 to +80 °C
In use: Max. +80 °C
Rated position (NL)
Any
Weight
Approx. 0.12 kg
Capillary
2,000 mm including 460 mm protective tubing as standard, min. bending radius of the capillary 5 mm
Material no. Cu-DHP
Electrical connection
Snap-action switch with single-pole changeover contact
Switching capacity
TR / TW
STW
STB
On the N/C contact (contact deck 1-2):
AC 400 V +10 %, 16 A, AC 230 V +10 %, 16 (2.5) A, cos
ϕ = 1 (0.6), DC 230 V+10 %, 0.25 A
Switching capacity
On the N/O contact (contact deck 1-4):
AC 400 V +10 %, 6.3 A,
AC 230 V +10 %, 6.3 (2.5) A, cos
ϕ = 1 (0.6),
DC 230 V +10 %, 0.25 A
On the signal contact (contact deck 1-4):
AC 400 V +10 %, 2 A,
AC 230 V +10 %, 2 (04) A, cos
ϕ = 1 (0.6),
DC 230 V +10 %, 0.25 A
Snap-action switch with gold plating - extra code 702: AC / DC 24 V, 0.1 A)
Electrical connection
A 6.3-0.8 according to DIN 46244
Switching reliability
To ensure the greatest possible switching reliability, we recommend a minimum load of:
AC / DC = 24 V, 100 mA for silver contacts
AC / DC = 10 V, 5 mA for gold-plated contacts (TZ 702)
Switching function
Rated value
Switching differential in %
of the control range span
TR / TW
2.5 %
Standard
TR / TW
7 %
Upon request
STW
7 %
Standard
Ambient temperature
influence
When the ambient temperature on the switching head and the capillary deviates from the calibration ambient
temperature of +22 °C, a switching point offset of approx. -0.1 K/K occurs.
Switching point accuracy
Switching differential
Scale beginning
Upper third
TR / TW 2.5 %
Standard
± 6 %
± 3 %
7 %
Upon request
± 8 %
± 4 %
STW / STB 7 %
Control range
In the "first half“
In the "second half“
+70 to 130 °C
+0/-12 K
+0/-5 K
+95 to 120 °C
+0/-5 K
+0/-5 K
+20 to 150 °C
+0/-15 K
+0/-10 K
+50 to 300 °C
+0/-30 K
+0/-15 K