Extra code ms (master-slave circuit) – JUMO 709040 TYA-110 thyristor power unit Data Sheet User Manual

Page 11

background image

3.2000 /00201355

Data Sheet 70.9040

M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany

Page 11/12

Suitable operating and control modes for different loads

X = suitable- = not suitable

Extra code MS (master-slave circuit)

Extra code
TR, TO
required

Operating mode

Load type

Temperature coefficient of load

constant

R

warm

= R

cold

positive

R

warm

> R

cold

negative

R

warm

< R

cold

long-term

ageing

non

phase-angle operation

X

-

-

-

yes

phase-angle operation
with current limiting

-

X

X

X

no

burst-firing operation

X

-

-

-

no

burst-firing operation
with initial phase-angle cut-back

X

-

-

-

yes

burst-firing operation
with initial phase-angle cut-back
and current limiting

-

X

X

X

Control mode

no

subsidiary U

2

control

X

X

-

-

yes

subsidiary I

2

control

-

-

X

-

yes

subsidiary P control

-

-

-

X

Mounting plate thickness: 5 mm
Units are wired up.

Mounting plate thickness: 10mm
Units are wired up.

Type TYA-110/3, 025… 100, …, MS …

Type TYA-110/3, 150… 250, …, MS …