beautypg.com

Technical data, Interfaces – JUMO 705060 mTRON T - Multifunction Panel 840 Data Sheet User Manual

Page 6

background image

2014-08-22/00529113

Data sheet 705060

Page 6/13

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866

1-800-554-5866

Fax:

315-437-5860

E-mail:

[email protected]

Internet: www.jumousa.com

Technical data

Interfaces

USB device interface

Connector designation

Setup

Connector type

Mini-B

Number

1

Application

To operate the setup program

Max. current

100 mA

USB host interface

Connector designation

USB1 and USB2

Connector type

A

Number

2

Application

For reading out data and configuration via memory stick

Max. current

100 mA

System bus In

Connector designation

Bus In

Connector type

RJ45

Number

1

Application

For connection of a base unit or router module

Connection cable

Network cable (patch cable or crossover cable), at least CAT5 (S/FTP)

Cable length

Up to 100 m

System bus Out

Connector designation

Bus Out

Connector type

RJ45

Number

1

Application

For connection of a router module

Connection cable

Network cable (patch cable or crossover cable), at least CAT5 (S/FTP)

Cable length

Up to 100 m

Ethernet

Connector designation

LAN

Connector type

RJ45

Number

1

Application

Communication with PC (setup program, data archiving, web server), e-mail server,
and Modbus master/slave

Protocols

TCP/IP, HTTP, DHCP, SMTP+POP3, Modbus/TCP

Baud rate

10 Mbit/s, 100 Mbit/s

RS232 or RS422/485 (serial interface)

Depending on the ordered device version

Connector designation

COM1 and COM2

Connector type

D-Sub

Number

2

Application

Communication with Modbus master/slave, connection of a barcode scanner or
modem including alarm transmission/message via text message or
e-mail

Protocol

Modbus RTU as master/slave, bar code scanner

Baud rate

9600, 19200, 38400

External inputs (external variables)

Via Modbus master/slave functions, 54 analog and 54 digital inputs