beautypg.com

Understanding and setting up the maxtek plo-10, Normal operation, Checkout – INFICON PLO-10i Phase Lock Oscillator User Manual

Page 19: Understanding and setting up the inficon plo-10 -1, Normal, Operation -1, Checkout -1

background image

PLO-10 PHASE LOCK OSCILLATOR

UNDERSTANDING AND SETTING UP THE INFICON PLO-10 2-1

2 UNDERSTANDING

AND

SETTING UP THE INFICON PLO-10

There are several LED’s on the PLO-10 to indicate its operation.
The green, Lock LED is on when the frequency is locked to a connected crystal’s

resonant frequency.
The Red, Unlock LED will be on whenever the frequency is not locked.
The Yellow, Sweep Rate LED flashes each time the frequency ramp is reset to its low

starting point.
The Reset switch allows you to force the VCO to its lowest frequency independently of

the Integrator output. The Reset switch also forces the Lock LED on, thus turning off the

quadrature current injection. The Quadrature current injection must be off to properly

adjust the capacitance cancellation. To insure that the VCO ramps up in frequency, a

small amount of quadrature current is injected into the current to voltage buffer whenever

the PLO is unlocked. This current is equivalent to a shunt capacitance of about 1.5 pfd.

As soon as lock is detected, the quadrature current is turned off.

2.1 NORMAL

OPERATION

The PLO-10 comes set up for operation with a INFICON cable and crystal holder. If a
INFICON

cable and crystal holder is being used, then no initial adjustments should be

needed.
During normal operation with a crystal installed and connected to the oscillator, the green

Lock LED will be on and the frequency output will reflect the crystal resonance. The red

Unlock LED will be off.
If the Unlock LED is on, the Sweep Rate LED should slowly flash. Continuous

sweeping of the frequency range indicates that the crystal’s resonant frequency is outside

of the PLO’s frequency range or the crystal’s conductance is below the conductance

threshold.
No flashing of the Sweep Rate LED when the Unlock LED is on can mean one of two

things. First, if the VCO frequency is sitting at its low limit, it means the electrode

capacitance is over compensated. Second, in some cases, even though the crystal

conductance has fallen below the threshold necessary to indicate lock, the internal signals

are still sufficient to keep the VCO locked to the crystal. In that case, the PLO really is

locked and the VCO frequency will be sitting at the crystal frequency somewhere

between its minimum and maximum frequencies.
If the VCO frequency is sitting at its low limit, press and hold the Reset switch and adjust

the fine capacitance trimmer a few degrees clockwise (not more than ten) until the Reset

LED begins to flash.

2.2

CHECKOUT

Make sure the wall mount power supply is specified for the voltage in your lab (120/240

volts).