NOTE: Settings can be checked using the

TEST/SETTINGS Button. See page 8 for details.

Setting the High Limit

The high limit is factory set at 190°F. To adjust, turn the HI

TEMP Dial

until the desired setting is displayed.

(Setting range: 100°-220°F)

Setting the Low Limit

The low limit is designed to maintain temperature in boil-

ers equipped with tankless coils used for domestic hot

water. The low limit is factory set to OFF. Prior to adjust-

ing, remove the jumper (not equipped on all units)

.

Then turn the LO TEMP Dial

clockwise until the

desired temperature is displayed. For proper operation,

the low temperature limit setting should be at least 10°

below the high limit setting. NOTE: For cold start opera-

tion, the low limit must be turned OFF. IMPORTANT: If low

limit temperature cannot be set above 140°F, remove

jumper

. (Setting range: OFF or 110°-200°F).

Setting the Economy Feature

The Economy Feature is factory set for a 1 zone heating sys-

tem. To adjust, turn the ECONOMY Dial

until the number

displayed equals the number of heating zones. Do not

include indirect water heaters in the number of heating

zones. The Economy Feature conserves fuel by reducing

boiler temperature (see “How Thermal Targeting Works”

below). If the heating system is unable to supply needed heat

to the house, the ECONOMY Dial should be turned to a lower

setting (example: In a three zone house, turn the dial to 2 or

1). Conversely, if the boiler provides adequate heat, added

fuel savings can be achieved by selecting a higher setting

(example: 4 or 5). If the heating and indirect water heater

signals were not separated when wiring the control, the

Economy Feature should be turned OFF to ensure the boiler

supplies

adequate

tempera-

ture to

heat the

indirect

tank.

7

SETTING THE CONTROL

HOW THERMAL TARGETING WORKS

SYSTEM START-UP

Dynamic

Display

Water Temperature

and Real Time

Verification of

Setting Adjustments.

Low Temperature

Limit Setting

(OFF or 110°-200°F)

Factory OFF

High Temperature

Limit Setting

(100°-220°F)

Factory 190°F

Diagnostic LEDs

and Test Button

Jumper

Economy Dial

(OFF or LO, 1, 2, 3,

4, 5, HI)

Differentials

are automatic

and will vary

based on

control settings

and boiler tem-

perature.

Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house requires. When it

is very cold outside, the heat demand is high and the Fuel Smart HydroStat will raise the boilerʼs Target temperature to provide

needed heat to the home. When the outside temperature is milder, the heat demand is lower. During these periods, the Fuel

Smart HydroStat will lower the boilerʼs Target temperature – saving fuel – while continuing to provide comfort to the house.

SETTING

Disables economy function. Will allow boiler to fire until
hi-limit temp is reached and re-fire with a 10° subtractive
differential.

Provides lowest level of fuel savings. Use this setting only
if the house does not stay warm at higher settings.

Recommended setting for single zone systems

Recommended setting for Two zone systems

Recommended setting for Three zone systems

Recommended setting for Four zone systems

Recommended setting for Five zone systems

Provides highest level of fuel savings

Zone/Indirect

Switch

Setting the Zone/Indirect Switch

See WIRING on page 4-6.

Activating Thermal Pre-Purge (optional)

NOTE: Activation of this feature is not

recommended for boilers with tankless coils.

Fuel Smart HydroStat has a Thermal Pre-Purge feature to

maximize efficiency. When activated, the control will purge

higher boiler temperatures down to 135° at the start of any

thermostat call and supply the latent energy in the boiler to the

heating zone that is calling. During the purge cycle, the dis-

play will indicate Pur. If the heat is not sufficient to satisfy the

thermostat, the control will energize the burner. This feature

works with single- and multi-zone heating systems utilizing cir-

culators or zone valves. No change in wiring is needed.
To Activate Thermal Pre-Purge

Push and hold the TEST/SETTINGS button for 20 seconds.

The display will read Pur On. To deactivate the feature, push

and hold the button a second time for

20 seconds. The display will read Pur OFF.

At initial start up, with the Economy Feature active, the control establishes a 145°F target temperature. To test the high limit

shut-off function, the Economy Dial must be turned to OFF. Once tested, restore the Economy setting. If the heating demand is

high, the target will increase over time to satisfy the heat load. NOTE: To reduce the potential for condensing, the control

will allow the boiler to heat to 120°F prior to energizing the circulator.