beautypg.com

Hydrolevel 700 Series User Manual

Page 2

background image

A1

Connect the hot lead of the input

voltage (24 VAC, 60 HZ) to terminal 1. Connect
the neutral lead to terminal 2. 24 VAC, 60 HZ
must be supplied to terminals 1 and 2 for inter-
nal operation of the control.

Install a jumper between terminal

A2

1 and terminal P1. Power from terminal P1 is
supplied to terminal P2 through the control
relay when water is at the probe.

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

NEUTRAL

HOT

2

1

ALARM

P1

P2

A

HOT

BURNER
CIRCUIT

NEUTRAL

2

1

BURNER

POWER

SOURCE

(24 or

120VAC)

P1

P2

A

BURNER

POWER

SOURCE

24VAC

60HZ

2

1

2

P1

P2

A

BURNER

POWER

SOURCE

24VAC

60HZ

1

NEUTRAL

HOT

P1

P2

A

NEUTRAL

HOT

BURNER

+

0

LIMIT

CONTROLS

2

1

2

P1

P2

A

BURNER

POWER

SOURCE

24VAC

60HZ

1

NEUTRAL

HOT

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

HOT

NEUTRAL

2

1

1

P1

P2

A

ALARM

WIRING METHOD A: SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

B1

Connect the hot lead of the input

voltage (24 VAC, 60 HZ) to terminal 1. Connect
the neutral lead to terminal 2. 24 VAC, 60 HZ
must be supplied to terminals 1 and 2 for inter-
nal operation of the control.

Connect hot lead from the 24 VAC
or 120 VAC burner power source to
terminal P1. This terminal supplies power to ter-
minal P2 in normal operating conditions when
water is at the probe. Connect neutral to burner
circuit. Note: consult boiler manufacturer
instructions for proper terminal connections.

A3

Connect terminal 2 to burner circuit

neutral. Connect terminal P2 to burner circuit in
series with other limit controls. Consult boiler
manufacturer instructions for proper terminal
connections. Control should be wired in series
with and before other circuits.

Optional alarm connection.

A4

Connect alarm common to terminal 2.
Connect alarm hot to terminal A.

Upon completion of wiring, replace control
box cover.

B3

Connect terminal P2 to burner

circuit in series with and before other limit con-
trols.

Optional alarm connection. Connect

B4

alarm hot to terminal A. Connect alarm common
to neutral of the burner power source.

Upon completion of wiring, replace control
box cover.

A1

A2

A3

A4

B1

B3

B2

B4

WIRING METHOD B: SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

B2

This manual is related to the following products: