Error messages – HYDAC EDS 601 User Manual

Page 10

background image

Zero point

Final value

Sensor

30 .. 120
digits

850 .. 1015

Output current

0 .. 300 digits

300 .. 1020 (10 digits 0.11
V)

Notes:

l

The calibration should only be altered by a qualified person.

l

Calibration is possible in the following ranges:

(All details in digits, based on 10 bit values = max. 1023)

l

The zero point always refers to the lower measuring range limit, i.e. to the

pressure value 0 bar, not to the measured value 0. (The two are only

identical if the measuring range begins at 0).

l

The signal range can be made compatible by specifically changing the zero

point and the final value of the analogue output, e.g. to 0..5 V, 1..5 V,

0..20 mA, 0..10 mA

l

If the measuring range is not given in bar, incorrect measuring ranges can

arise due to the conversion, e.g., a 40 bar pressure switch which is

designed to be operated in the converted unit kN has a measuring range of

5.14 kN due to the conversion. By re-calibrating the unit it can be operated

as a 5 kN unit. For this purpose, change the measuring range to 5.00 and

calibrate the final value of the sensor to this value. This is especially

sensible when making use of the analogue output, as the 10 V signal now

corresponds to a value of 5.00 kN, no longer 5.14 kN.

Disabling the programming

To prevent accidental re-programming of the settings, the programming can be

disabled. To enable or disable the programming the D and Ñ keys must be

pressed simultaneously. After approx. 5 seconds "PROG“ appears in the

display. Afterwards the condition of the programme disable is displayed and can

be changed with the D and Ñ keys.

l

"ON“ means programming enabled

l

"OFF“ means programming disabled

Once the PROG key has been pressed the condition of the programme enable

is saved in the memory and the unit reverts to the normal display (primary

display). If the programming is disabled ("PROG“ = "OFF“) all the settings can

still be viewed but not altered.

Error messages

Operating errors

ER 01

Error when setting the switching points and switch-back hystereses.

The switching hysteresis is either too large for the pre-set switching

point or the measuring range was altered so much that the

switching point lies outside the measuring range.

ER 02

Error when setting the measuring range.

ER 03

Error when setting the calibration data.

ER 04

After the measuring range was altered the switching points or

switching hystereses lay outside the new range and were

automatically corrected to the standard value by the EDS 601.

Data errors

For these errors to be understood, the following needs to be explained:
The settings with which the unit is operated are stored in a RAM. This memory

loses its contents, however, if the unit is no longer supplied with voltage. All

settings are stored in a second memory, an EEPROM. Whenever settings are

altered the data is written into the EEPROM from the RAM. When, however,

voltage is supplied they are then read back into the RAM from the EEPROM.