Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used. See Service Manual for
triple evacuation method.

Always break a vacuum with dry

nitrogen._

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 4)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS 2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 4 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal

box cover removed.

Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT

PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 5 -- Line Power Connections

Connect Control Wiring

Route low--voltage control wires through control wiring grommet
and connect leads to control board.
For Evolution, connect to ABCD only.

For standard

non--communicating thermostats, connect to standard thermostat

connections R, C, Y1 and Y2.
Use No. 18 AWG color--coded, insulated (35_C minimum) wire
for all installations.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer or fan coil transformer for control power,

24--v/40--va minimum. The outdoor unit requires a minimum of
27va/24 vac control power.

Final Wiring Checks

IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

Furnish power to crankcase heater a minimum of 24 hr before

starting unit. To furnish power to heater only, set thermostat to
OFF and close electrical disconnect to outdoor unit.
NOTE: On 187A models, starting the compressor without a
minimum of 12 hours of crankcase heat prior to initial start--up
may result in a compressor chattering noise and possible damage to
the compressor.

Install Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.