The control is shipped with the brownout active. The change in
status is remembered until toggled to a new status. A power

down/power up sequence will not reset the status. It may be
necessary to do the toggle twice to cycle to the desired state of the

defeat.

230V Line (Power Disconnect) Detection

If there is no 230v at the compressor contactor(s) when the indoor
unit is powered and cooling demand exists, the appropriate error

code is displayed (see Table 6). Verify that the disconnect is closed

and 230v wiring is connected to the unit.

Compressor Voltage Sensing

The control board input terminals labeled VS, VR and L2 on 187A

models and VS and L2 on 180A models (see Fig. 6) are used to

detect compressor voltage status, and alert the user of potential
problems. The control continuously monitors the high voltage on

the run capacitor of the compressor motor. Voltage should be
present any time the compressor contactor is energized, and voltage

should not be present when the contactor is de--energized.

Contactor Shorted Detection

If there is compressor voltage sensed when there is no demand for
compressor operation, the contactor may be stuck closed or there is

a wiring error. The control will flash the appropriate fault code.

187A Models, Compressor Thermal Cutout

The control senses the compressor voltage at VR and VS. When
starting or running, a phase difference of the voltages on the inputs

will indicate the thermal protector is closed. If the phase difference
is 5 degrees or less for 10 seconds, the internal protector is open.

The control de--energizes the appropriate compressor contactor for

15 minutes, but continues to operate the outdoor fan. The control
Status LED will flash the appropriate code shown in Table 6. After

15 minutes, with a call for low-- or high--stage cooling, the
appropriate compressor contactor is energized. If the thermal

protector has not re--set, the outdoor fan is turned off. If the call for

cooling or heating continues, the control will energize the
compressor contactor every 15 minutes. If the thermal protector

closes, (at the next 15 minute interval check), the unit will resume
operation.
If the thermal cutout trips for three consecutive cycles, then unit
operation is locked out for 4 hours and the appropriate fault code is

displayed.

180A Models, Compressor Thermal Cutout

If the control senses the compressor voltage after start--up, and is
then absent for 10 consecutive seconds while cooling demand

exists, the thermal protector is open. The control de--energizes the

compressor contactor for 15 minutes, but continues to operate the
outdoor fan. The control Status LED will flash the appropriate

code shown in Table 6. After 15 minutes, with a call for low-- or
high--stage cooling, the compressor contactor is energized. If the

thermal protector has not re--set, the outdoor fan is turned off. If

the call for cooling continues, the control will energize the
compressor contactor every 15 minutes. If the thermal protector

closes, (at the next 15 minute interval check), the unit will resume
operation.
If the thermal cutout trips for three consecutive cycles, then unit
operation is locked out for 4 hours and the appropriate fault code is

displayed.

Low or High Contactor Open (187A models) / No 230V

at Compressor (180A models)

If the compressor voltage is not sensed when the compressor

should be starting, the appropriate contactor may be stuck open or
there is a wiring error. The control will flash the appropriate fault

code. Check the contactor and control box wiring.

187A Models Only, Compressor Start Detection

In low--stage, if the specified start voltage at VR terminal is not

achieved, the start relay is de--energized after 1 second and the
control will flash the appropriate fault code.
In high--stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de--energized after 1 second and the

control will flash the appropriate fault code.
If the specified start voltage is not achieved for 3 consecutive

low--stage starts, low--stage operation is locked out for 30 minutes.

If the specified start voltage is not achieved for 3 consecutive
high--stage starts, high--stage operation is locked out for 30

minutes. The control will flash the appropriate fault code.

Troubleshooting 187A units for proper switching

between low-- & high--stages

Check the suction and liquid pressures at the service valves.
Suction pressure should be reduced by 5--10% when switching

from low to high capacity. There should be a 10--20% increase in

liquid pressure when switching from low to high capacity.
Compressor current should increase 100--250% when switching

from low to high--stage.

Troubleshooting 180A units for proper switching

between low-- & high--stages

Check the suction pressures at the service valves. Suction pressure
should be reduced by 3--10% when switching from low to high

capacity.
NOTE: The liquid pressures are very similar between low-- and
high--stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20--45% when switching from

low-- to high--stage. The compressor solenoid when energized in

high--stage, should measure 24vac.
When the compressor is operating in low--stage the 24v DC

compressor solenoid coil is de--energized. When the compressor is
operating in high--stage, the 24v DC solenoid coil is energized.

The solenoid plug harness that is connected to the compressor has

an internal rectifier that converts the 24v AC signal to 24v DC.

DO NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER.

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by

the DC solenoid, that modulates between high-- and low--stage. If

it is suspected that the unloader is not working, the following
methods may be used to verify operation.

1. Operate the system and measure compressor amperage.

Cycle the unloader on and off at 30 second plus intervals at

the UI (from low-- to high--stage and back to low--stage).
Wait 5 seconds after staging to high before taking a reading.
The compressor amperage should go up or down at least 20

percent.

2. If step one does not give the expected results, remove the

solenoid plug from the compressor and with the unit run-
ning and the UI calling for high--stage, test the voltage out-

put at the plug with a DC voltmeter. The reading should be
24 volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance. The
resistance should be 32 to 60 ohms depending on com-

pressor temperature. If the coil resistance is infinite, much
lower than 32 ohms, or is grounded, the compressor must
be replaced.

180A