beautypg.com

4 dip switch settings, 5 led indicator, Manual eks electronic-key adapter profibus-dp – EUCHNER EKS FSA with Profibus-DP Interface User Manual

Page 14

background image

Manual EKS Electronic-Key Adapter Profibus-DP

4.4 DIP switch settings

The device address 0...126 (decimal) can be set using the DIP switches S1 to S7. The device address is given
by the sum of the address values on each DIP switch.

Write protection can be enabled using DIP switch S8. In this way the writing of data to the Electronic-Key
read/write is prevented.

Information!

The settings are only applied when the power supply is switched on.

DIP switches, 8-pole:

DIP

switch

Factory setting

Functions

address 3

S8

ON = write protection for Electronic-Key read/write

OFF

S7

ON = address

64 decimal

OFF

S6

ON = address

32 decimal

OFF

S5

ON = address

16 decimal

OFF

S4

ON = address

8 decimal

OFF

S3

ON = address

4 decimal

OFF

S2

ON = address

2 decimal

ON

S1

ON = address

1 decimal

ON

The device addresses 0 to 126 (decimal) are set using the following scheme:

1 2 3 4 5 6 7 8

ON

Device

LSB

MSB

address

S1

S2

S3

S4

S5

S6

S7

S8

0 OFF OFF OFF OFF OFF OFF OFF
1

ON OFF OFF OFF OFF OFF OFF

2 OFF ON OFF OFF OFF OFF OFF
3

ON ON OFF OFF OFF OFF OFF

:

32 OFF OFF OFF OFF OFF ON OFF

:

126 OFF ON ON ON ON ON ON

Write

protection

for

Electronic-

Key

read/write

Information!

The address 126 is only intended to be used for setup purposes.

4.5 LED

indicator

The Electronic-Key adapter operating states are indicated using a 3-color LED on the front.
Illumination of the LED in any color indicates the presence of the operating voltage.

Color

Operating state

Description
General bus error.

Red Fault

No communication with the bus master or error when the Electronic-Key is written or
read (e.g. due to premature removal of the key from the Electronic-Key adapter or a
faulty key).
The LED then flashes red for approx. 5 s. After this, the LED is illuminated green again
and the Electronic-Key adapter is again ready for use.

Green Ready

Communication with the bus master without Electronic-Key, Electronic-Key adapter
ready.

Yellow Electronic-Key

active

Communication with the bus master with Electronic-Key. There is an Electronic-Key in
the Electronic-Key adapter and it has been detected.

092009-03-10/07

Subject to technical modifications

Page 14

/