Connection of a single ESL

If a single ESL is used, connect the device as shown in Figure 3. The OD output

can also be connected here to a control system as a monitoring output.
The device can be reset via the RST input. To do this, a voltage of 24 V is applied

to the RST input for at least 3 seconds. The supply voltage to the switch is inter-

rupted during this time. The RST input must be connected to 0 V if it is not used.

GND

DC 24 V

ESL-AR #1

FI1B
1

UB
2

FO1A
3

FO1B
4

M12 plug-connector

(8-pin)

OD
5

FI1A
6

0V

7

RST
8

-K1

-K2

-M1

M

A1

A2

A1

A2

13

14
13

14

Figure 3: Connection example for a single ESL-AR

Warning!

In case of an error, loss of the safety function through incorrect connection.

Ì

To ensure safety, both safety outputs (FO1A and FO1B) must always be eval-
uated. Single-channel use of the safety outputs leads to a reduction of the
category in accordance with EN ISO 13849-1.