Operating Instructions Safety System CES-A-ABA-01/CES-A-ABA-01B

14

Setup

LED indicators

STATE

LED green

Normal operation

Flashing

Teach-in

operation (for further signal function

see status table)

OUT

LED yellow

Valid actuator detected

ERROR

LED red

- Test input activated

- Internal electronics fault

- Invalid teach-in operation

(see status table)

Reset

In case of operating faults, the evaluation unit can be reset to the operating state
by interrupting the power supply for approx. 10 seconds.

Teach-in function for actuator

The actuator must be assigned to the evaluation unit using a teach-in function
before the system forms a functional unit. During a learning process, the safety
outputs are open and the door monitoring output is at LOW, i.e. the system is in
a safe condition.

Important!

Ì

Repeated teach-in of the same actuator on the same evaluation unit is not
possible.

Ì

The number of teach-in operations on one evaluation unit is limited to a maxi-
mum of 8

Ì

The evaluation unit can only be operated with the last actuator taught

Ì

A teach-in operation is invalid if:

Ì

the teach-in operation is cancelled before the green flashing LED goes out

Ì

the power supply is switched off during the teach-in operation

Ì

When the evaluation unit is switched on (operating voltage is applied), the
STATE LED signals the number of possible remaining teach-in operations
(see system status table)

Ì

After the eighth teach-in operation or if an "old" actuator is placed against the
read head, the system automatically switches to the teach-in mode. In both
cases, a teach-in operation with a duration of 60 seconds is started; how-
ever, the last actuator code remains active (see system status table) in the
memory – a new code is not taught.