27
Operating Instructions MGB-L0...AR.-... and MGB-L0...AP.-...
11.3 Electrical function test
Warning!
On usage in a switch chain with different AR devices (CES-AR, CET-AR), also follow
the procedure for the functional check in the related system manual.
1. Switch on operating voltage.
¨
The locking module carries out a self-test. In case of AR configuration: The
green State LED flashes for 8 s with 5 Hz.
2. Close all safety guards and insert the bolt tongue in the locking module. As
soon as the bolt tongue is inserted in the interlocking module, the safety
outputs FO1A/FO1B are ON.
¨
The machine must not start automatically.
¨
The green State LED illuminates continuously.
3. Enable operation in the control system.
4. Open the safety guard.
¨
The machine must switch off and it must not be possible to start it as long as
the safety guard is open.
Repeat steps 2-4 for each safety guard.