Operating Instructions MGB-L0...AR.-... and MGB-L0...AP.-...

10.6 Notes on operation with control systems

General notes

Do not use a control system with pulsing or switch off the pulsing function

in your control system. The device generates its own pulsed signal for short

circuit monitoring on the output lines FO1A/FO1B. A downstream control

system must tolerate these pulses, which may have a length of up to 1 ms.

The pulses are also present when the safety outputs are switched off (only on FO1A).

Depending on the inertia of the connected device (control system, relay, etc.), this

can lead to short switching processes (only on configuration as AR device).
There must also not be any pulsed signals on the inputs (FI1A/FI1B). The MGB is

connected statically to 24 V DC (connection comparable with light barriers, OSSD)
Do not use a control system with pulsing or switch off the pulsing function in

your control system. The device generates its own pulsed signal for short cir-

cuit monitoring on the output lines FO1A/FO1B. A downstream control system

must tolerate these pulses, which may have a length of up to approx. 300µs.

The pulses are not present when the safety outputs are switched off.
The inputs on an evaluation unit connected must be positive-switching, as the two

outputs on the safety switch deliver a level of +24 V in the switched-on state.

Note:

Due to the fact that the short circuit monitoring is undertaken by the device
itself, the Performance Level in accordance with EN 13849 is not reduced if the
control system pulsing is switched off.