3 requirements for connection cables, 4 notes on cable laying, Requirements for connection cables – EUCHNER MGB-L0-xxxAPx-xxx User Manual
Page 19: Notes on cable laying
19
Operating Instructions MGB-L0...AR.-... and MGB-L0...AP.-...
10.3 Requirements for connection cables
Caution!
Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.
Ì
On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.
Observe the following requirements with respect to the connection cables:
Parameter
Value
Unit
Wire cross-section min.
0.13
mm²
R max.
60
W
/km
C max.
120
nF/km
L max.
0.65
mH/km
10.4 Notes on cable laying
Ì
Lay all MGB connection cables in a common cable harness.
Important: lay cables in a common harness
Figure 15: Stipulated cable laying
PLC
+ 24 V DC
cabinet
0 V
MGB-L.-...
FI1A/
FI1B
FO1A/
FO1B
UB 0V UA 0V