Operating Instructions Safety Switch SGP-TW...

(Twin)

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Inspection and Service

If damage or wear is found, the complete switch
and actuator assembly must be replaced.

Replacement of individual parts or assemblies
is not permitted!

No servicing is required, but regular inspection of
the following is necessary to ensure trouble-free long-
term operation:

correct switching function
secure mounting of components
dirt and wear
sealing of cable entry
loose cable connections.

Safety switches must be completely replaced after 1
million operating cycles.

Note: The year of manufacture can be seen in the
bottom, right corner of the rating plate.

Exclusion of Liability under the Following
Conditions:

if the unit is not used for its intended purpose
non-compliance with safety regulations
installation and electrical connection not performed
by authorized personnel.
failure to perform functional checks.

Declaration of Conformity

See Annex 1 of the operating instructions.

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

100872-04-05/10 (translation of the original operating instructions)

Figure 3: Switching elements and switching functions

34

34

42

42

22

22

12

12

12

12

22

22

42

42

34

34

14

22

22

42

42

34

34

21

22

14

13

11

12

22

21

22

12

14

22

21

11

13

21

41

42

34

33

33

41

21

11

22

21

11

12

12

11

21

22

11

21

41

33

33

34

42

41

14

13

21

22

13

21

41

33

33

34

42

41

1

2

3

4

5

6

4

5

6

7

8

11

9

3

2

1

10

Version

Switching contacts

SGP-TW-.-528H...

1 NC contact +
1 NO contact

SGP-TW-.-538H...

2 NC contacts

SGP-TW-.-2121H...

4 NC contacts

SGP-TW-.-2131H...

3 NC contacts +
1 NO contact

SGP-TW-.-3131H...

2 NC contacts +
2 NO contacts

Door closed

Door open

Plug connector

SR6

Plug connector

SR11

2.

1

2.

2

3

4

1.

1.

6

5

Ordinal numbers of
switching elements

2.

1.

1.

2.

3.

3.

4.

4.

6

8

5

7

4

3

2

1

Ordinal numbers of
switching elements

Contact assignment with

plug connector

Connector
illustration

(view of safety switch

connection side)

(LED indicator with full wiring options, optional)

Technical Data

Parameters

Value

Housing material

Reinforced thermoplastic

Degree of protection according to IEC 60529
SGP-TW-1...

IP67

SGP-TW-2...

IP65

Mech. Mechanical life

1x10

6

operating cycles

Ambient temperature

-20 ... +80°C

Degree of contamination
(external, according ?to

3 (industrial)

EN 60947-1)
Installation position

Any

Approach speed, max.

20 m/min

Actuating force

25 N

Actuation frequency, max.

6700 / h

Extraction force

25 N

Retention force

10 N

Switching principle

Slow-action switching contact

Contact material

Silver alloy, gold flashed

Connection type
SGP-TW-1...

Screw terminal

SGP-TW-2...SR6

Plug connector SR6, 6-pin+PE

SGP-TW-2...SR11

Plug connector SR11, 11-pin+PE

Conductor cross-section (rigid/flexible)
SGP-TW-1...

0.34...1.5 mm²

SGP-TW-2...SR6

0.5...1.5 mm²

SGP-TW-2...SR11

0.5 mm²

Operating voltage for
optional LED indicator

L060

12 - 60 V

(only SGP-TW...528H/

L110

110 V

SGP-TW...538H)

L220

230 V

Switching voltage min.

12 V

at 10 mA
Switching current, min.,
at 24 V

1 mA

Short circuit protection
(control circuit fuse)

4 A gG

according to IEC 60269-1
Conv. thermal current I

th

4 A

Utilization category

SGP-TW-1.../

according to EN 60947-5-1

SGP-TW-2...SR6

SGP-TW-2...SR11

AC-15

4 A 230 V

4 A 50 V

DC-13

4 A 24 V

4 A 24 V

Rated impulse
withstand voltage

U

imp

= 2.5 kV

Rated insulation voltage

U

i

= 250 V

Reliability figures according to EN ISO 13849-1
B

10d

2 x 10

6