Handheld & Panel Mount - Remove the top cover on
the controller with a phillips screwdriver.
OEM Interface Module - Remove the cover with
a phillips screwdriver to locate the USB port.
PRESET – Opens or closes the valve to a preset position
o
To Change Valve Preset, move the valve to the desired position.
o
Press and hold the PRESET button for 10 seconds
o
The PRESET button will now bring the valve into this position when pressed outside of Setup
Mode
TRIGGER (Joystick Only) – When the Joystick TRIGGER is pulled, the valve will begin opening and
stay open as long as the TRIGGER remains pulled. When the TRIGGER is released, the valve will
close.
L. Auxiliary
Turn on/off optional light 1 – Hold AUX and press FOG
Turn on/off optional light 2 – Hold AUX and press STREAM
M. Write Diagnostic File
Power up all EXM system components.
Remove the USB cover from any input controller. (If the system has more than one controller
select the one with the easiest access. See illustration below for locations of the USB connection)
Install a blank USB flash drive into the USB port of the desired input controller, and the controller
will automatically enter USB Mode (The following LED routines should occur to indicate USB
mode has been initiated. If USB Mode does not initiate, hold AUX and OSC for 2 seconds and
watch for the LED indicators)
o
If using a panel mount or hand held, the yellow status LED on the controller will begin to
blink at once per second intervals.
o
If using Joystick, all valve LEDs will flash once to indicate that you are in USB Mode
Press and release the OPEN button. The LED above the open button will flash while the
information is being downloaded.
A diagnostic file called EBDIAG.CSV is written to the USB flash drive. When the LED above the
open button begins flashing at a 3 second interval, the download is complete.
Remove the USB from the input controller to leave USB Mode. (On older systems it may be
necessary to push the right button on the panel mount or hand held, or move the joystick right, to
exit USB mode).
Contact Elkhart Brass to make arrangements to send the EBDIAG.CSV file for review.