Det-Tronics X2200 UV Flame Detector User Manual
Page 16

95-8549
14
13.1
startup proceDure
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEsT
1. Disable any extinguishing equipment that is
connected to the system.
2. Apply input power to the system.
3. Initiate an
oi
test. (See “Magnetic
oi
/ Manual
oi
”
under Optical Integrity in the Description section of
this manual.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
6. Enable extinguishing equipment when the test is
complete.
troubleshooting
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
3. Check input power to the unit.
4. If the fire system has a logging function, check
the fire panel log for output status information.
See Table 4 for information regarding 0 to 20 mA
output.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. If all wiring checks out and cleaning of the
oi
plate/
window did not correct the fault condition, check for
high levels of background UV radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background UV radiation is present. Re-adjust the
view of the detector away from the UV source or
relocate the detector.
If none of these actions corrects the problem, return the
detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
maintenance
Important
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
NOTE
Refer to the X2200 Safety manual (95-8672) for
specific requirements and recommendations
applicable to the proper installation, operation,
and maintenance of all SIL-Certified X2200 Flame
Detectors.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X2200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
table 4—current Level output troubleshooting guide
Current Level
(±0.3 mA)
status
Action
0 mA
Power Fault
Check system wiring.
1 mA
General Fault
Cycle power.1
2 mA
oi
Fault
Clean windows.2
4 mA
Normal Operation
16 mA
Hi Background UV
Fault
Remove UV source
or aim detector away
from UV source.
20 mA
Fire Alarm