Det-Tronics X3302 Multispectrum IR Flame Detector with Pulse Output User Manual
Page 10

95-8578
6.1
8
Important
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14
mm hex wrench to ensure that the mounting arm
assembly is tight.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
+
–
(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1
oi DRIVER
D1-2
oi DRIVER
D1-3
oi DRIVER
D1-4
oi DRIVER
D1-5
oi DRIVER
D1-6
oi DRIVER
D1-7
oi DRIVER
D1-8
oi DRIVER
D2-1
oi DRIVER
D2-2
oi DRIVER
D2-3
oi DRIVER
D2-4
oi DRIVER
D2-5
oi DRIVER
D2-6
oi DRIVER
D2-7
oi DRIVER
D2-8
oi DRIVER
DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8
FIRE LOGIC “A”
FIRE LOGIC “B”
ALARM OUTPUT
EXTERNAL RESET/INHIBIT
OUTPUTS INHIBITED
FAULT OUTPUT
EXTERNAL ACCEPT
STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8
DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7
CHASSIS (EARTH) GND
J1-7
J1-15
J1-5
J1-13
J1-6
J1-14
J1-8
J1-16
J1-9
J1-17
J1-10
J1-18
J1-11
J1-19
J2
R7404 CONTROLLER
J1
10 TO 38 VDC
#2
#1
#19
#22
X3302
DETECTOR 1
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 2
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 3
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 4
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 5
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 6
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 7
#2
#1
#19
#22
#2
#1
#19
#22
X3302
DETECTOR 8
#2
#1
#19
#22
A2266
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
24
VDC
+
–
62
63
64
TO J1-2
0.47 µF / 400 VDC
NON-POLARIZED
GROUND FAULT PROTECTED SYSTEMS
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi
("D" LEAD)
TERMINAL IDENTIFICATION FOR X3302
WITH PULSE OUTPUT.
NOTE: DO NOT CONNECT THE X3302 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
DMA IN AVAILABLE
}
figure 6—a Typical System, X3302 Detectors Wired to R7404 Controller