beautypg.com

Troubleshooting: error messages and alarm, Table 7. error messages and next steps – Despatch Stackable LCC/LCD-4 User Manual

Page 44

background image

T

ROUBLESHOOTING

Stackable LCC/LCD Oven Owner

’s Manual

44

Version 1.1

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.

7.

Troubleshooting: Error Messages and Alarm

Table 7 lists the more common error messages, the possible problems and remedies.

Table 7. Error Messages and Next Steps.
Alarm Status

Possible Problem

Next Step

Hi-Limit LED flashing

Problem with thermocouple

Hi-limit setpoint has been
exceeded.

Once the problem has corrected,
press Reset.

Soak LED flashing

Oven temperature has not
entered (or dropped out of) the
soak band and the soak timer
has stopped

Program a slower ramp rate or if
oven is not heating check heater
circuit.

Top LED displays
OPEN and lower LCD
displays CONTROL
SENS ERR

Control thermocouple is
disconnected or broken

Repair or replace the thermocouple.

Lower LCD displays HI
LIM SENS ERR

Hi limit thermocouple is
disconnected or broken

Repair or replace the thermocouple.

Lower LCD displays
HIGH LIMIT ALARM

Hi limit temperature setpoint
has been exceeded

Determine if:

the setting is too close to the
setpoint

the SSR is defective

calibration is incorrect



The lower LCD intermittently displays
HL Temp. This is not an
error message, but the Hi limit thermocouple temperature
reading.