17

7. While observing O2 Analyzer readout, adjust zero

pressure regulator [ZPR] (A) and main adjustment

screw [MAS] (B) to obtain stoichiometric value shown

in table below. Select table value that corresponds to

your O2 measurement system. Shaded table line is

target value.

8. Set generator’s main circuit breaker ON.
9. Apply full load to generator. Adjust MAS (B) to achieve

target value. Clockwise rotation of MAS will cause air-

fuel mixture to become more lean.

10. Set generator’s main circuit breaker OFF (no load).

Adjust ZPR (A) to achieve target value. Clockwise

rotation of ZPR will cause mixture to become more

rich. Make sure ZPR tower cap is reinstalled prior to

final reading.

11. Set generator’s main circuit breaker ON (resume full

load). Reverify sensor value remains in target area.

Adjust MAS (B) as necessary.

12. Set generator’s main circuit breaker OFF (no load).

Reverify sensor value remains in target area. Adjust

ZPR (A) as necessary.

13. Set the generator’s main circuit breaker OFF.
14. Push and hold the MANUAL OVER-RIDE button on

control panel. When the engine stops, allow it to cool

for a few minutes before proceeding.

15. Remove O2 sensor from exhaust manifold and reinstall

plug. Disconnect timing light from engine.

16. Complete emissions statement and send with

installation checklist.

A

B

Voltage

Phi

Lamda

2.40

1.000

1.000

2.45

1.012

0.988

2.50

1.024

0.977

2.55

1.036

0.966

2.60

1.048

0.955

2.65

1.060

0.944

2.70

1.071

0.933