beautypg.com

Briggs & Stratton 30000 SERIES User Manual

Page 16

background image

16

BRIGGSandSTRATTON.COM

Battery
The installer must supply a sealed, rechargeable 12 Volt DC,

650 Cold Cranking Amps (CCA) 55 amp hour starting

battery. The battery may not be at full charge when installed.

If battery voltage is below 12 Volts, charge the battery. See

Battery in Maintenance for details.
NOTE: DO NOT use a deep-cycle type battery.

Fuel Supply System

Ensure that all fuel pipe connections are tight, secure and

without leaks.
Ensure that all gas line shutoff valves are OPEN and that

adequate fuel pressure is available whenever automatic

operation is desired.

Initial Start-up (No Load)

Before operating the home generator or placing it into

service, inspect the entire installation carefully.
Then begin testing the system without any electrical loads

connected, as follows:
NOTE: Unit has been set-up for natural gas operation at the

factory. Fuel conversion, if needed, must be completed prior

to performing these steps.
1. Set generator’s main circuit breaker to its ON (closed)

position.

2. Confirm 15 Amp fuse is installed in control panel.
3. Set generator’s system switch to AUTO.
4. Push MANUAL OVER-RIDE button on control panel.
NOTE: When the generator is started for the very first time, it

will require that air in the gaseous fuel lines be purged. This

may take a few minutes.
5. DO NOT crank engine for more than 15 seconds, then

pause for 15 seconds to reduce heat in the starter.

6. Repeat process until engine starts.
7. Listen for unusual noises, vibration or other indications

of abnormal operation. Check for oil or coolant leaks

while engine runs.

8. Let engine warm up for about five minutes to allow

internal temperatures to stabilize.

9. Connect an accurate AC voltmeter and a frequency

meter to check generator output at load side of circuit

breaker. No-load voltage should be 239-244 Volts,

frequency should be 59.8 - 60.2 Hz.

NOTE: If AC voltage is outside these ranges, perform the

generator adjustment, Steps 13 and 14 below.
10. Check generator output between one of the generator

connection lugs and the neutral lug, then between the

other generator connection lug and the neutral lug.

In both cases, voltage reading should be between

117-123 Volts.

11. Push and hold

MANUAL OVER-RIDE button on control

panel again until engine stops.

IMPORTANT: DO NOT proceed until you are certain that

generator AC voltage is correct and within the stated limits.

Generator frequency is fixed and not adjustable
12. If voltage and frequency values are correct, proceed to

step 15.

13. Connect voltmeter as described in step 9 above.
14. While observing voltmeter, adjust alternator voltage

control (A) for 240 volts. DO NOT adjust either of the

other alternator controls.

15. Install alternator circuit breaker enclosure cover.
16. Close all enclosure access doors.

Fuel Conversion

The unit is shipped from the factory calibrated for NG

operation. To convert the engine from NG to LP vapor

operation, follow these steps:

1. Disconnect NEGATIVE battery cable from battery.
2. Set the generator’s main circuit breaker OFF.
3. Set the control panel System switch to OFF.
4. Install O2 sensor into exhaust manifold.
NOTE: Avoid leaving O2 sensor attached for lengthy period.
5. After purging fuel supply line, push MANUAL OVER-

RIDE button on control panel. When the engine starts,

allow it to warm up for a few minutes under no load.

6. Attach a timing light to engine. Loosen distributor

hold-down clamp. While one person observes timing

indicator, a second person adjusts distributor for

20º before top dead center. Tighten distributor hold-

down.

NOTE: If converting from LP to NG, use 32º before top dead

center.

UNDER-FREQ.

ADJUST

ST

ABILIT

Y

ADJUST

VO
LT

AGE

ADJUST

A